B369_Boiler
Response Deadline
May 11, 2026, 4:00 PM(CDT)10 days
Eligibility
Contract Type
Sources Sought
The scope of work is to provide a new NTI model LX-600 boiler; 600,000 BTU input, with ASME SS heat exchanger, floor-mount, factory-provided ASME relief valve, at least 4 to 1 turn down, 95% combustion efficiency, 4” exhaust vent and 4” fresh air intake, with outdoor sensor, CSD-1 controls, integrated electronic controller with touch screen access, and factory-installed condensate trap and included condensate drain kit.
The hydronic gas boiler must be at least 600 MBH capacity, with at least 4:1 turndown on natural gas, and dimensions no larger than 24"wide x 47.5"deep(long) x 55" high, with water (2") and gas (1") connections along the left-hand length side and air inlet/exhaust (4") connections along the top or left-hand length side.
The Contractor shall provide at least a 1-year comprehensive warranty on all new materials.