1) Can you please confirm with the client for the compressor do they want oil free rotary screw? Or oil flooded rotary screw?
Normally you see desiccant dryers with oil free applications but wanted to confirm with you.
Answer: Oil free screw type
2) Is the requested compressor intended to be a current Quincy model, a legacy Quincy model, or a brand neutral performance specification?
Answer: Brand neutral
3) The current Quincy QGSV 25 is variable speed and direct drive, and its current public table lists 125.1 cubic feet per minute at 100 pounds per square inch gauge. The current QGD 25 is gear driven and fixed speed, and its current public table lists 109.8 cubic feet per minute at 125 pounds per square inch gauge. What exact current model or combination satisfies variable speed, gear drive, 25 horsepower, and 117.6 cubic feet per minute at 125 pounds per square inch gauge?
Answer: The model selected should be as close to matching Quincy QGDV series unit
4) Is a current Original Equipment Manufacturer controller accepted if the named Q Control Touch controller is unavailable on the compliant
25 horsepower model.
Answer: No we want the Q-Control Touch Controller as a way to monitor compressors performance and maintenance status
5) Must the compressor and 120 gallon horizontal receiver be factory mounted as one package?
Answer: Yes
6) Please identify the required discharge connection, working pressure, relief setting, air quality, ambient conditions, altitude, ventilation, maximum sound level, electrical full load current, disconnect, starter, dryer dew point, filter grades, pressure drop, separator drain, condensate treatment, and any installation boundary.
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
Page 3 of 3
Answer: Air compressor to be used in Indianapolis. This is for supply and delivery-not installation. 125 psig working pressure, discharge connection shall be standard for Quincy QGVD-25 unit. Use Quincy specs for the remainder of your questions.
7) Does factory startup include electrical energization, piping, anchoring, configuration, testing, training, and a written startup report, or only an authorized technician visit after Government installation?
Answer :Authorized start up shall be sufficient to obtain extended warranty per Quincy True Blue requirements
8) What delivery date, site access, receiving, inside delivery, rigging, offload, acceptance, and invoice timing apply?
Answer: Supplier will deliver and off load to Shops dock at the VAMC, Indianapolis. VA forces will move from dock and install.
9) May Sentiq remain the prime and seller of record while an authorized local Quincy distributor supplies, delivers, starts, and services the package?
Answer: Yes so long as Quincy provides the warranty
10) What is the intended usage of the system? Medical Air, Instrument Air, Compressed Air, etc.
Answer: General shops and control system air supply
11) Is this a single compressor, or should it be duplexed?
Answer: Single compressor
12) Is this material and parts only, or does this include installation? This includes factory startup which makes it seem like we are supposed to provide installation.
Answer: VA will receive and transport from dock to use site. VA personnel will plumb, connect electricity to compressor. Factory start up will be to inspect, start and provide services as required to make unit eligible for extended warranty
DEPARTMENT OF VETERANS AFFAIRS
DEPARTMENT OF VETERANS AFFAIRS
250-NETWORK CONTRACT OFFICE 10 (36C250)
250-NETWORK CONTRACT OFFICE 10 (36C250)
VISN 10 CONSOLIDATED CONTRACTING
4100 WEST 3RD STREET
DAYTON, OH, 45428
NAICS
Air and Gas Compressor Manufacturing
PSC
COMPRESSORS AND VACUUM PUMPS
Set-Aside
Total Small Business Set-Aside (FAR 19.5)