Loading...
W9127N26QA080
Response Deadline
May 13, 2026, 9:00 PM(EDT)6 days
Eligibility
Contract Type
Sources Sought
Sources Sought Number: W9127N26QA080
Subject: Sources Sought for vertical lineshaft pumps
PSC: 4320 - Power and Hand Pumps
NAICS: 333914 - Measuring, Dispensing, and Other Pumping Equipment Manufacturing
General. This Sources Sought is issued for informational and market research purposes only. It is not a Request for Proposal (RFP), Request for Quotation (RFQ), Invitation for Bid (IFB), or a solicitation under FAR Subpart 5.2.
The purpose of this Sources Sought is to obtain information regarding industry interest, capabilities, and qualifications so the Government can make informed acquisition decisions. We encourage responses from both large and small businesses, including Small Business, Small Disadvantaged Business, 8(a) firms, HUBZone firms, Woman-Owned Small Business (WOSB), Economically Disadvantaged Woman-Owned Small Business (EDWOSB), Service-Disabled Veteran-Owned Small Business (SDVOSB), and Veteran-Owned Small Business (VOSB). All interested parties are strongly encouraged to respond.
Responses to this Sources Sought will be used by the Government to support market research, assess available sources, and inform any future solicitation.
Please provide a capability statement demonstrating your ability to supply the requirement identified in the Performance Work Schedule (PWS). If you are unable to supply all of the listed items, please clearly identify any limitations in your capability statement.
This will help us accurately assess your qualifications for the full requirement.
Formal Sources Sought Response Due: 13 May 2026 at 12:00 PM PDT.
Project Background:
The U.S. Army Corps of Engineers (USACE) requires two (2) vertical lineshaft pumps for Big Cliff Powerhouse.
Outlet: 4” 150# ANSI 16.5 Flange compatible
Flow: 75 GPM at 70ft head
Static Head: 70 ft
Pump Curve: Continuously rising
Pump Formfactor: Vertical lineshaft with multistage impellers at inlet
Pump Height: 45’ from inlet to centerline of outlet flange
Lineshaft: 1” diameter, 5’ sections, 400 series stainless steel
Lineshaft Couplings: Coupling design capacity shall be the published manufacturer service rating divided by 1.5
Lineshaft Bearings: Water lubricated except for motor base bearing which may use oil or grease
Impeller Material: Bronze
Bowl Material: Cast Iron
Prelubrication: If needed, a prelubrication water line will be provided
Column Pipe: 5’ sections with flanged connections, 400 series stainless steel
Pumped Media: Potentially silty water, temperature ranging 39°-65° F
Filtering: Inlets must have basket strainers
Motors: Up to 3.0 hp with a service factor of 1.15 or greater
Motor Power Supply: 3 phase, 480 V, 60 hz circuit
Pump Speed: 1800 rpm or less
DEPT OF DEFENSE
DEPT OF THE ARMY
US ARMY CORPS OF ENGINEERS
ENGINEER DIVISION NORTHWESTERN
ENDIST PORTLAND
W071 ENDIST PORTLAND
W071 ENDIST PORTLAND
KO CONTRACTING DIVISION
333 SW FIRST AVE
PORTLAND, OR, 97204-3495
NAICS
Measuring, Dispensing, and Other Pumping Equipment Manufacturing
PSC
POWER AND HAND PUMPS
Set-Aside
No Set aside used